1. Home
  2. UA Family Help
  3. Utilizing UA20B – Water Leak Sensor

Utilizing UA20B – Water Leak Sensor

Thank you for purchasing DEKIST UA20-B.

UA20-B is designed to support 12VDC power output terminal and 4-20mA 1 channel. Therefore, the leak detection function can be conveniently used by configuring the leak sensor and the resistor in parallel.

준비물

1. Water leak sensor: AutoSensorKorea (LASK – MCB-18) using the model

2. 1.5 kΩresistance

3. UA20B

1. Connecting the UA20B water leak sensor

1. Check the channels on the back of the UA20-B. With the USB port facing up, the terminal block of 4 consists of a 12VDV power output and a 4-20mA signal input on the left.

UA20-B rear view detail

2. Leakage sensor (LASK – MCB-18) cable red/green wireV out 12V DC Output + Connect to the terminal (first from the left).

3. Water leak sensor (LASK – MCB-18) cable white/black wireCH1 4-20mA Analog Signal Input Terminal +to the terminal (third from left).

4. V out 12V DC Output + Terminal and 4-20mA Analog Signal Input Terminal + to the terminal 1.5㏀ resistanceconnect it.

Leak sensor wiring and 20 to UA1.5-B terminal block resistance connection diagram

2. Setting up Radionode UA Calibration

  1. The input mode is changed to 0~20mA. The factory default for input mode is 4-20mA.
  2. If there is no leakage: The minimum value of 4mA is output.
Output value in case of no leak

3. When moisture is detected in the sensor part: The amount of water and the numerical value are directly proportional. (Max. 20mA)

Output value in case of small leakage
Output value in case of a lot of leakage
Updated on January 2022, 2

Was this article helpful?

Related Articles