Thank you for purchasing DEKIST UA20-B.
UA20-B is designed to support 12VDC power output terminal and 4-20mA 1 channel. Therefore, the leak detection function can be conveniently used by configuring the leak sensor and the resistor in parallel.
준비물
1. Water leak sensor: AutoSensorKorea (LASK – MCB-18) using the model
2. 1.5 kΩresistance
3. UA20B
1. Connecting the UA20B water leak sensor
1. Check the channels on the back of the UA20-B. With the USB port facing up, the terminal block of 4 consists of a 12VDV power output and a 4-20mA signal input on the left.
2. Leakage sensor (LASK – MCB-18) cable red/green wireV out 12V DC Output + Connect to the terminal (first from the left).
3. Water leak sensor (LASK – MCB-18) cable white/black wireCH1 4-20mA Analog Signal Input Terminal +to the terminal (third from left).
4. V out 12V DC Output + Terminal and 4-20mA Analog Signal Input Terminal + to the terminal 1.5㏀ resistanceconnect it.
2. Setting up Radionode UA Calibration
- The input mode is changed to 0~20mA. The factory default for input mode is 4-20mA.
- If there is no leakage: The minimum value of 4mA is output.
3. When moisture is detected in the sensor part: The amount of water and the numerical value are directly proportional. (Max. 20mA)